Welcome to GAPS Water Treatment learn more

Fast delivery starting from £9.00 Learn more

Order online, email or call with you order!

Our office will be closed from December 20th to January 6th.

Wishing you a Merry Christmas and a prosperous New Year!

B Series Reverse Osmosis System

SKU: BSRO-1
£5,652.00
Tax included Shipping calculated at checkout.


The B-series is the simplest of our reverse osmosis systems and unlike the C-series it doesn't have flow gauges, pressure gauges and a TDS meter. It is however built to the same high standards on a 304 stainless steel skid and using a high quality pump and membranes.

The B series RO systems recovery rate is 75%. All B-series ROs have an integrated carbon filter to remove chlorine to prevent membrane damage.

Pre-treatment:
RO plants must be supplied with softened and de-chlorinated water. A duplex softener is recommended for continuous operation. Utilizing softened water for the feed to the RO will reduce the scaling potential on the membrane and therefore lengthen its working life. De-chlorination of the feed will reduce oxidation damage to the surface of the membrane. Membranes can also be fouled by Iron, Manganese, organics and microorganisms. For boreholes and other private supplies a full water analysis is advised before installing an RO so that a pre-treatment system can be specified.

Site Requirements

The site requirements of an RO on site are vital for its successful operation. Apart from the RO requiring a certain quality of water, free from potential foulants, the system must be fed with sufficient volume and pressure. The flush phase of an RO requires more water than during normal service. The flush phase flow rates can be found in more information.

The site should also have sufficient space to allow siting, installation and ongoing maintenance. system) control the operation of the RO. A delivery pump (suitable for use with RO water) may be used to boost the treated water to service.

The diagram above shows a typical plumbing layout involving a reverse osmosis system. The softened water is fed to a Carbon cartridge filter on the inlet to the B-series RO. Water is then forced at high pressure through the membranes and the resulting permeate can then be collected in the permeate storage tank. Level probes (which are included in the RO system) control the operation of the RO. A delivery pump (suitable for use with RO water) may be used to boost the treated water to service.

Payment & Security

Payment methods

  • American Express
  • Apple Pay
  • Diners Club
  • Discover
  • Google Pay
  • Maestro
  • Mastercard
  • PayPal
  • Union Pay
  • Visa

Your payment information is processed securely. We do not store credit card details nor have access to your credit card information.