Sita LCD Range Ultra Violet (UV) Systems (1.1 to 12 m3/hr)

Sita LCD Range

Sita LCD Range

The LCD series UV-C systems are composed of:
-Stainless steel reactor that contains the special germicidal lamps
-Control panel, made in compliance with the CE standard

Main Application:
Water Disinfection for: - Private water
- Light industrial process water
- Food & Beverage industry

Certification:
CE, WRAS, GOST

Technical description:
Flow rates: from 1 to 12 m3/h (depending on UV –C trasmittance value)
UV-C dose after 9000 hr: 300 - 400 J/m2 (depending on UV model)
Power: from 30 W to 160 W
Connections: threated connection
Lamps: High efficiency low pressure lamps
Lamps lifespan: 9.000 hrs
Sensor: UV-C selective sensor (only on Plus models)
Max Pressure: 10 bars (optional 16 bars)
Temperature range: 0 – 40 °C
UV reactor material: Stainless steel 316L
Control Panel material: Plastic material
Stainless Steel Reactor

Stainless Steel Reactor

The UV reactor is totally in stainless steel AISI 304 or 316L internally/externally polished; the stainless steel of its chemical/physical characteristics is particularly suitable for the treatment of primary waters, and being polished also in the internal part it is completely without porosity that could favour the keeping of spores; moreover, being glass polished, the germicidal action of the lamps is increased.

Configuration
: U shape (405 and 412 models) Z shape (440, 480, 550 and 80/2 models)
Mounting: Vertical
Connections: Female threated
UV sensor holder: Stainless steel 316L
UV sensor: Selective sensor (option: DWGV or O-Norm Sensor)
Seals: Silicone and Viton
Control Panels

Control Panels

The electrical control panel supplied is ready for the installation (complete of all the necessary cables).

- Polypropylene control box
- Protection class: IP 54
- Status messages
- Microprocessor control - Total hour meter
- Resettable hour meter (only on Plus version)
- Control of each lamp
- Alarm 220 V NA/NC outlet - Alarm Free contact outlet - Remote on/off (optional)
- 4-20 mA outlet (optional)
- UV intensity: % (only on Plus version)
- Control of temperature - irradiation (pre set alarm threshold) (only on Plus version)
- Temperature Range: (0-40°C)

Sita LCD Range